Quadruplex Aluminum Conductor 600V URD

Quadruplex Aluminum Conductor 600V URD

Clear

Enter the total length in feet you'll need. You can specify different reel lengths in the put up field.

Optional. Enter your required feet per reel in the following format #reels X #feet. For example, for 1,000 feet on three reels you might enter: 1x500,2x250. You may enter as many reels as you need. Make sure your put ups match for your total length.

Reels Qty:

Enter the number of reels you desire at the specified length - for example you can order 2 put ups of 500 feet of cable. Also you can add the same product to your quote for separate lengths per reel. For example if you need a reel of 500 feet and an additional reel of 100 feet.

DWC Part #: N/A Categories: ,
View Spec Sheet

Description

Quadruplex Aluminum URD has a 600 volt rating and is designed to be used in secondary distribution circuits where you are installing in ducts or in a direct burial type of application. The maximum operating temperature is 90 degrees Celsius in both wet and dry conditions.

Conductor: Aluminum

Insulation: Cross Linked Polyethylene (XLP)

Additional information

DWC Part # TulsaDykeWittenbergNotre DamePurdueSyracuseDavidsonWake ForestEarlhamRustSlippery RockWofford
Phase Conductor AWG 4221/01/02/03/04/04/0250350500
Phase Conductor # of Strands 777191919191919373737
Phase Conductor Insulation Thickness (in) 0.060.060.060.080.080.080.080.080.080.0950.0950.095
Neutral AWG 44221/013/02/04/03/04/0350
Neutral # of Strands 77771919191919191937
Neutral Insulation Thickness (in) 0.060.060.060.060.080.080.080.080.080.080.080.095
Diameter Single Phase Conductor (in) 0.3450.3450.4030.4030.5120.4730.6030.5550.6580.760.6580.831
Diameter Complete Cable (in) 0.8310.9740.9741.2381.2381.3411.4521.5861.5861.762.0082.184
Weight (lbs / 1000ft) 2593483785446006608719811063118715402183
Allowable Ampacities Direct Burial (amps) 119153153198198225250290290325385465
Allowable Ampacities In Duct (amps) 85115115150150170195225225250305370