| Type: VNTC Tray Cable With Ground | ![]() |
| VNTC | 600 Volts | 90C THHN/PVC | Power Sizes Multi-Conductor | Bare Copper |
|
| DWC Catalog Number | Size AWG/ kcmil | # of Conductors | # of Strands | Nylon Jacket Thickness In Mils | Insulation Thickness In Mils | Jacket Thickness In Mils | Ground Wire AWG | O.D. Inch | Weight Lbs/M |
|---|---|---|---|---|---|---|---|---|---|
| 0803VNGTC | 8 | 3 | 7 | 5 | 30 | 60 | 10 | 0.58 | 220 |
| 0804VNGTC | 8 | 4 | 7 | 5 | 30 | 60 | 10 | 0.61 | 286 |
| 0603VNGTC | 6 | 3 | 7 | 5 | 30 | 60 | 8 | 0.69 | 386 |
| 0604VNGTC | 6 | 4 | 7 | 5 | 30 | 60 | 8 | 0.76 | 505 |
| 0403VNGTC | 4 | 3 | 7 | 6 | 40 | 60 | 8 | 0.89 | 630 |
| 0404VNGTC | 4 | 4 | 7 | 6 | 40 | 80 | 8 | 0.97 | 828 |
| 0203VNGTC | 2 | 3 | 7 | 6 | 40 | 80 | 6 | 1.03 | 930 |
| 0204VNGTC | 2 | 4 | 7 | 6 | 40 | 80 | 6 | 1.13 | 1213 |
| 0103VNGTC | 1 | 3 | 19 | 7 | 50 | 80 | 6 | 1.15 | 1252 |
| 1/003VNGTC | 1/0 | 3 | 19 | 7 | 50 | 80 | 6 | 1.22 | 1423 |
| 1/004VNGTC | 1/0 | 4 | 19 | 7 | 50 | 80 | 6 | 1.34 | 1832 |
| 2/003VNGTC | 2/0 | 3 | 19 | 7 | 50 | 80 | 6 | 1.32 | 1718 |
| 2/004VNGTC | 2/0 | 4 | 19 | 7 | 50 | 80 | 6 | 1.45 | 2223 |
| 3/003VNGTC | 3/0 | 3 | 19 | 7 | 50 | 80 | 4 | 1.42 | 2131 |
| 3/004VNGTC | 3/0 | 4 | 19 | 7 | 50 | 80 | 4 | 1.58 | 2756 |
| 4/003VNGTC | 4/0 | 3 | 19 | 7 | 50 | 80 | 3 | 1.54 | 2592 |
| 4/004VNGTC | 4/0 | 4 | 19 | 7 | 50 | 80 | 3 | 1.77 | 3457 |
| 25003VNGTC | 250 | 3 | 37 | 8 | 60 | 110 | 3 | 1.75 | 3123 |
| 25004VNGTC | 250 | 4 | 37 | 8 | 60 | 110 | 3 | 1.94 | 4046 |
| 35003VNGTC | 350 | 3 | 37 | 8 | 60 | 110 | 3 | 1.97 | 4204 |
| 35004VNGTC | 350 | 4 | 37 | 8 | 60 | 110 | 3 | 2.18 | 5469 |
| 50003VNGTC | 500 | 3 | 37 | 8 | 60 | 110 | 2 | 2.26 | 5792 |
| 50004VNGTC | 500 | 4 | 37 | 8 | 60 | 110 | 1 | 2.49 | 7556 |
| 75003VNGTC | 750 | 3 | 37 | 9 | 60 | 110 | 1 | 2.82 | 9060 |
Power sized tray cable (VNTC) with a non-insulated copper ground is used in 600 volt applications for power and control signals. It can be installed in ducts, trays, conduit and direct buried. Rated for Class 1, Div 2 hazardous locations.
Method 4 (M4) - A neutral or single-colored insulation compound is surface ink printed with conductor number to provide positive conductor identification through 21 conductors. The identification sequence is repeated for cables containing more than 21 conductors.