DWC Part # Size AWG # of Conductors Voltage Insulation Thickness In Mils Ground Wire AWG Armor O.D. Inch O.D. Inch Weight Lbs/M
1403Teck 14 3 600 30 14 0.62 0.71 255
1404Teck 14 4 600 30 14 0.67 0.76 266
1405Teck 14 5 600 30 14 0.70 0.79 321
1407Teck 14 7 600 30 14 0.76 0.85 345
1410Teck 14 10 600 30 14 0.88 0.96 451
1412Teck 14 12 600 30 14 0.90 0.99 511
1415Teck 14 15 600 30 14 0.96 1.04 586
1420Teck 14 20 600 30 14 1.13 1.21 789
1425Teck 14 25 600 30 14 1.22 1.30 958
1203Teck 12 3 600 30 14 0.66 0.75 280
1204Teck 12 4 600 30 14 0.73 0.82 341
1205Teck 12 5 600 30 14 0.77 0.86 372
1207Teck 12 7 600 30 14 0.83 0.91 443
1212Teck 12 12 600 30 14 1.01 1.10 972
1003Teck 10 3 600 30 12 0.71 0.80 339
1004Teck 10 4 600 30 12 0.78 0.87 400
1006Teck 10 6 600 30 12 0.88 0.96 532
1008Teck 10 8 600 30 12 0.93 1.02 791
0803Teck 8 3 1000 60 10 0.86 0.94 486
0603Teck 6 3 1000 60 8 1.04 1.13 724
0403Teck 4 3 1000 60 8 1.18 1.27 927
0203Teck 2 3 1000 60 6 1.30 1.39 1256
1/003Teck 1/0 3 1000 80 6 1.56 1.68 1906
2/003Teck 2/0 3 1000 80 6 1.65 1.77 2225
3/003Teck 3/0 3 1000 80 4 1.75 1.87 2666
4/003Teck 4/0 3 1000 80 4 1.86 1.98 3207
35003Teck 350 3 1000 90 3 2.26 2.40 4979
50003Teck 500 3 1000 90 3 2.52 2.66 6586

Teck 90 or Teck Style armored cables are used industrial and commercial applications in environments that require extra protection or durability. These cables can be direct buried and installed in conduit. uried. HL (Hazardous Location) rated.

  • Conductor: Stranded bare copper
  • Insulation: XLP
  • Armor: Aluminum interlocked armor
  • Jacket: Inner and Outer PVC
  • Flame Test: UL 1581 70,000 BTU/hour flame test
    Color Code:
    8AWG - 2AWG: Black, Red, Blue
    1/0 Larger and 10AWG and Smaller - Black with printed #'s