Distributor Wire & Cable
Spec Sheet


Type: Instrumentation Tray Cable Distributor Wire and Cable
VNTC | 600 Volts | 90C
TFN/PVC | Individual + Overall Shield
Triads | Bare Copper


DWC Part # Size AWG # of Triads PVC Insulation Thickness In Mils Nylon Jacket Thickness In Mils Overall Jacket Thickness In Mils O.D. Inch Weight Lbs/M
1804STOSVNTC 18 4 15 4 60 0.61 207
1808STOSVNTC 18 8 15 4 60 0.78 355
1812STOSVNTC 18 12 15 4 80 0.98 538
1824STOSVNTC 18 24 15 4 80 1.33 971
1604STOSVNTC 16 4 15 4 60 0.67 233
1608STOSVNTC 16 8 15 4 60 0.9 401
1612STOSVNTC 16 12 15 4 80 1.08 607
1616STOSVNTC 16 16 15 4 80 1.27 838
1624STOSVNTC 16 24 15 4 80 1.48 1100

Shielded VNTC instrumentation tray cables are used in 600 volt applications for process and control signals. Shielding protects the signal from eletrostatic noise and crosstalk. They can be installed in ducts, trays, conduit and direct buried. Rated for Class 1, Div 2 hazardous locations.

  • Conductor: Stranded bare copper
  • Insulation: PVC/TFN
  • Shield: Individually shielded triads + Overall shield
  • Jacket: PVC
  • Flame Test: UL 1581 70,000 BTU/hour flame test
    Color Code: