Type: Instrumentation Tray Cable Distributor Wire and Cable
VNTC | 600 Volts | 90C
TFN/PVC | Individual + Overall Shield
Bare Copper


DWC Part # Size AWG # of Pairs PVC Insulation Thickness In Mils Nylon Jacket Thickness In Mils Overall Jacket Thickness In Mils O.D. Inch Weight Lbs/M
1802SPOSVNTC 18 2 15 4 45 0.44 82
1804SPOSVNTC 18 4 15 4 45 0.52 146
1808SPOSVNTC 18 8 15 4 60 0.71 279
1812SPOSVNTC 18 12 15 4 60 0.85 391
1816SPOSVNTC 18 16 15 4 80 1.05 494
1824SPOSVNTC 18 24 15 4 80 1.2 752
1836SPOSVNTC 18 36 15 4 80 1.37 1053
1850SPOSVNTC 18 50 15 4 80 1.71 1300
1602SPOSVNTC 16 2 15 4 45 0.48 105
1603SPOSVNTC 16 3 15 4 45 0.56 136
1604SPOSVNTC 16 4 15 4 60 0.63 207
1606SPOSVNTC 16 6 15 4 60 0.77 257
1608SPOSVNTC 16 8 15 4 60 0.81 349
1612SPOSVNTC 16 12 15 4 80 1.00 528
1616SPOSVNTC 16 16 15 4 80 1.12 623
1619SPOSVNTC 16 19 15 4 80 1.23 790
1624SPOSVNTC 16 24 15 4 80 1.39 944
1636SPOSVNTC 16 36 15 4 80 1.59 1331
1650SPOSVNTC 16 50 15 4 110 1.96 1731

Shielded VNTC instrumentation tray cables are used in 600 volt applications for process and control signals. Shielding protects the signal from eletrostatic noise and crosstalk. They can be installed in ducts, trays, conduit and direct buried. Rated for Class 1, Div 2 hazardous locations.

  • Conductor: Stranded bare copper
  • Insulation: PVC/TFN
  • Shield: Individually shielded pairs + Overall shield
  • Jacket: PVC
  • Flame Test: UL 1581 70,000 BTU/hour flame test
    Color Code: