Distributor Wire & Cable
Spec Sheet


Type: Power Limited Tray Cable Distributor Wire and Cable
PLTC | 300 Volts | 105C
PVC | Individual + Overall Shield | Bare Copper


DWC Part # Size AWG # of Pairs Insulation Thickness In Mils Jacket Thickness In Mils O.D. Inch Weight Lbs/M
2002SPOSPLTC 20 2 15 40 0.36 61
2004SPOSPLTC 20 4 15 50 0.46 110
2008SPOSPLTC 20 8 15 50 0.58 182
2012SPOSPLTC 20 12 15 60 0.71 267
2016SPOSPLTC 20 16 15 60 0.81 315
2024SPOSPLTC 20 24 15 70 0.97 492
2036SPOSPLTC 20 36 15 70 1.11 685
2050SPOSPLTC 20 50 15 70 1.33 768
1802SPOSPLTC 18 2 15 40 0.4 76
1804SPOSPLTC 18 4 15 50 0.5 134
1808SPOSPLTC 18 8 15 50 0.63 226
1812SPOSPLTC 18 12 15 60 0.78 332
1816SPOSPLTC 18 16 15 60 0.89 374
1824SPOSPLTC 18 24 15 70 1.08 619
1836SPOSPLTC 18 36 15 70 1.23 869
1850SPOSPLTC 18 50 15 80 1.49 1047
1602SPOSPLTC 16 2 15 50 0.47 107
1604SPOSPLTC 16 4 15 50 0.55 178
1608SPOSPLTC 16 8 15 60 0.73 323
1612SPOSPLTC 16 12 15 60 0.87 456
1616SPOSPLTC 16 16 15 70 1.02 529
1624SPOSPLTC 16 24 15 70 1.21 860
1636SPOSPLTC 16 36 15 80 1.4 1250
1650SPOSPLTC 16 50 15 80 1.68 1453

Power limited tray cables (PLTC) are used in ducts, trays and conduit audio, intercom, alarm and other 300 volt instrumentation circuits. Shielding provides protection from electrostatic noice and crosstalk. Rated for Class 1, Div 2 hazardous locations.

  • Conductor: Stranded bare copper
  • Insulation: PVC
  • Shield: Individually shielded pairs + Overall shield
  • Jacket: PVC
  • Flame Test: UL 1581 70,000 BTU/hour flame test
    Color Code: