Distributor Wire & Cable Spec Sheet

Type: 300 Volt CLX Armored Cable Distributor Wire and Cable
Corflex - Continuously Welded Armor | Instrumentation
Type MC | 600 Volt | PLTC | 105C
Shielded Pairs + Overall Shield | PVC Jacket


DWC Part # Size AWG # of Pairs Insulation Thickness In Mils Jacket Thickness InMils Armor O.D. Inch Inner Jacket O.D. Inch Inner Jacket Thickness In Mils O.D. Inch Weight Lbs/M
1802SPOSPLTCCLX 18 2 Pair 15 40 0.58 0.38 40 0.66 185
1804SPOSPLTCCLX 18 4 Pair 15 50 0.70 0.46 50 0.80 271
1808SPOSPLTCCLX 18 8 Pair 15 50 0.84 0.59 50 0.94 385
1812SPOSPLTCCLX 18 12 Pair 15 60 1.02 0.74 60 1.14 540
1824SPOSPLTCCLX 18 24 Pair 15 70 1.33 1.02 70 1.47 920
1836SPOSPLTCCLX 18 36 Pair 15 70 1.51 1.17 70 1.65 1190
1601POSPLTCCLX 16 1 Pair 15 35 0.40 0.25 35 0.47 110
1601TOSPLTCCLX 16 1 Triad 15 35 0.44 0.27 35 0.51 129
1602SPOSPLTCCLX 16 2 Pair 15 50 0.66 0.44 50 0.76 241
1603SPOSPLTCCLX 16 3 Pair 15 50 0.70 0.47 50 0.80 280
1604SPOSPLTCCLX 16 4 Pair 15 50 0.74 0.51 50 0.84 316
1604STOSPLTCCLX 16 4 Triad 15 50 0.84 0.58 50 0.94 400
1606SPOSPLTCCLX 16 6 Pair 15 50 0.88 0.61 50 0.98 410
1608SPOSPLTCCLX 16 8 Pair 15 60 0.97 0.68 60 1.09 511
1612SPOSPLTCCLX 16 12 Pair 15 60 1.13 0.82 60 1.25 670
1624SPOSPLTCCLX 16 24 Pair 15 70 1.46 1.14 70 1.60 1165
1636SPOSPLTCCLX 16 36 Pair 15 80 1.71 1.33 80 1.87 1615

Can be used in many industrial and commerical applications where high reliability and durability is required. Found in many harsh environments and recommended as an economical alternative in conduit systems. Installed in wet or dry locations as well as direct buried. Class 1 Div 2 for hazardous location.

  • Conductor: Stranded bare copper
  • Insulation: PVC
  • Shield: Indiviudal shield + Overall shield on each pair or triad
  • Inner Jacket: PVC
  • Armor: Continuously welded armor
  • Jacket: PVC
  • Flame Test: UL 1581/ICEA 70,000 BTU/hr flame test/IEEE 383
    Color Code:

    Distributor Wire and Cable | Direct: 720.317.2277 | Fax: 720.317.2278 | www.distributorwire.com