Distributor Wire & Cable
Spec Sheet


Type: PE-86 Outside Plant Phone Cable Distributor Wire and Cable
PE-86 | Direct Burial
Multi-Paired | 8 Mil Shield | Double Jacket


DWC Part # Size AWG # of Pairs O.D. Inch Weight Lbs/M
2202PE86 22 2 0.31 40
2203PE86 22 3 0.33 49
1902PE86 19 2 0.37 59
1903PE86 19 3 0.43 79

PE-86 outside plant phone cable is used in direct burial applications and in aerial applications when supported by a messenger.

  • Conductor: Solid bare copper
  • Insulation: Solid polyolefin
  • Filling Compound: The entire core assembly is completely filled with ETPR compound, filling the interstices between the pairs and under the core tape.
  • Inner Jacket: Black, linear low-density polyethylene
  • Shield: Corrugated, copolymer coated .008" (8 mil) tape applied longitudinally with an overlap
  • Outer Jacket: Black, linear low-density polyethylene
    Color Code:
    Cond. No. Color Code Cond. No. Color Code
    1 White w/ Blue Band 14 Black w/ Brown Band
    2 White w/ Orange Band 15 Black w/ Gray Band
    3 White w/ Green Band 16 Yellow w/ Blue Band
    4 White w/ Brown Band 17 Yellow w/ Orange Band
    5 White w/ Gray Band 18 Yellow w/ Green Band
    6 Red w/ Blue Band 19 Yellow w/ Brown Band
    7 Red w/ Orange Band 20 Yellow w/ Gray Band
    8 Red w/ Green Band 21 Purple w/ Blue Band
    9 Red w/ Brown Band 22 Purple w/ Orange Band
    10 Red w/ Gray Band 23 Purple w/ Green Band
    11 Black w/ Blue Band 24 Purple w/ Brown Band
    12 Black w/ Orange Band 25 Purple w/ Gray Band
    13 Black w/ Green Band - -

    Distributor Wire and Cable | Direct: 720.317.2277 | Fax: 720.317.2278 | www.distributorwire.com