Type: 5KV/8KV Power Cable Distributor Wire and Cable
Three Conductor | EPR Insulation | PVC Jacket
EPR Insulation | PVC Jacket - 5KV/133% | 8KV/100%
Copper Tape Shield | 105C


DWC Part # Size AWG # of Strands Insulation Thickness In Mils Jacket Thickness In Mils Insulation O.D. Inch Ground Size O.D. Inch Weight Lbs/M
06035KVSEPRPVC 6 7 115 80 0.47 6 1.38 1052
04035KVSEPRPVC 4 7 115 80 0.52 6 1.48 1265
02035KVSEPRPVC 2 7 115 80 0.57 6 1.61 1608
01035KVSEPRPVC 1 19 115 110 0.61 4 1.75 1989
1/0035KVSEPRPVC 1/0 19 115 110 0.65 4 1.84 2257
2/0035KVSEPRPVC 2/0 19 115 110 0.7 4 1.93 2609
3/0035KVSEPRPVC 3/0 19 115 110 0.75 3 2.04 3073
4/0035KVSEPRPVC 4/0 19 115 110 0.8 3 2.16 3598
250035KVSEPRPVC 250 37 115 110 0.86 3 2.3 4094
350035KVSEPRPVC 350 37 115 110 0.96 2 2.52 5288
500035KVSEPRPVC 500 37 115 140 1.09 1 2.89 7256
750035KVSEPRPVC 750 61 115 140 1.28 1 3.77 10128

5KV/8KV power cables are recommended for use as feeder circuits, distribution circuits, and for feeders or branch circuits in commercial and industrial applications. Installed in wet or dry locations or direct buried. 1/0 and larger are CT (Cable tray) rated.

  • Conductor: Stranded bare copper
  • Insulation: Ethylene propylene rubber (EPR)
  • Shield: Copper tape shield
  • Jacket: PVC Jacket
  • Flame Test: IEEE 383 70,000 BTU/hr flame test
  • Color Code: Method 4 (M4) - A neutral or single-colored insulation compound is surface ink printed with conductor number to provide positive conductor identification through 21 conductors. The identification sequence is repeated for cables containing more than 21 conductors.