Distributor Wire & Cable Spec Sheet

Type: 2.4KV Armored Cable Distributor Wire and Cable
2.4KV Multi-Conductor Interlocked Armor
133% EPR Insulation | Non-Shielded
105C | CT Use


DWC Part # Size AWG # of Conductors # of Strands Insulation Thickness In Mils Jacket Thickness In Mils Ground Wire AWG Armor O.D. Inch O.D. Inch Weight Lbs/M
06032.4KVAIAPG 6 3 7 115 50 6 1.19 1.30 905
04032.4KVAIAPG 4 3 7 115 50 6 1.29 1.40 1115
02032.4KVAIAPG 2 3 7 115 50 6 1.42 1.53 1430
01032.4KVAIAPG 1 3 19 115 50 4 1.50 1.61 1770
1/0032.4KVAIAPG 1/0 3 19 115 60 4 1.59 1.72 2025
2/0032.4KVAIAPG 2/0 3 19 115 60 4 1.72 1.85 2390
3/0032.4KVAIAPG 3/0 3 19 115 60 3 1.83 1.96 3000
4/0032.4KVAIAPG 4/0 3 19 115 60 3 1.95 2.08 3395
250032.4KVAIAPG 250 3 37 115 60 3 2.07 2.20 3900
350032.4KVAIAPG 350 3 37 115 75 2 2.30 2.46 5105
500032.4KVAIAPG 500 3 37 115 75 1 2.57 2.73 6800
750032.4KVAIAPG 750 3 61 115 85 1 2.98 3.14 9400

Medium voltage power cables are recommended for use as feeder circuits, distribution circuits, and for feeders or branch circuits in commercial and industrial applications. Installed in wet or dry locations or direct buried.

  • Conductor: Stranded bare copper
  • Insulation: Ethylene propylene rubber (EPR)
  • Armor: Aluminum interlocked armor (AIA). Special order for galvanized steel armor.
  • Jacket: Yellow PVC Jacket
  • Color Code: Method 4 (M4) - A neutral or single-colored insulation compound is surface ink printed with conductor number to provide positive conductor identification through 21 conductors. The identification sequence is repeated for cables containing more than 21 conductors.